PHLEEN F7-200 SMART PLC provides an integrated control solution for a 3.8 km coastal highway tunnel. With 24 interconnected control cabinets, the system enables coordinated control of tunnel ventilation, lane indicators, traffic monitoring, and drainage operations.Weight measurement modules integrated into an automated batching and filling line

In this project, PHLEEN F7-200 SMART used to build the tunnel Area Control Units (ACUs). A single control system integrates functions such as tunnel gas concentration detection and automatic fan ventilation control, lane indicator control, water level detection and automatic drainage control, fire detection and automatic fire suppression linkage, and traffic flow detection. The system has been successfully commissioned and put into operation.The entire tunnel is 3.8 kilometers long and consists of 24 interconnected control cabinets, enabling real-time monitoring and control of the tunnel’s status.

 Name  Model  I/O Specifications Function
Programma Logic Controller CPU SR6 DI36 / DO 24 Host CPU, core controller, with built-in Ethernet port + RS485 (Modbus); the table lists 3 Modbus ports, used to interface with CO/VI detectors, soft-start/variable-frequency drives for fans, upper-level monitoring systems, and fire alarm interlock signals
Digital I/O Expansion Module EM DR32 DI16 / DO16 Expands DI inputs to monitor fan operation, faults, and manual/automatic mode feedback; DO outputs control fan start/stop and status indicator lights
Digital I/O Expansion Module EM DE16 DI16 DI expansion; acquires signals from sensors, contactor auxiliary contacts, lane indicator status, and dry contact fire alarm signals
Digital I/O Expansion Module  EM QR08 DO8 8-point relay output; low-capacity control points: indicator lights, alarms, and lane indicator control circuits

System Architecture and PLC Selection

PHLEEN F7-200 SMART PLC features a modular architecture with flexible I/O configurations. Selected digital output modules provide isolated relay outputs for reliable load control, while the digital input modules support signal acquisition from field devices.

PHLEEN F7-200 SMART PLC features three-proof protection, helping improve resistance to moisture, salt fog, and dust in demanding industrial environments. their modular design allows for flexible configuration—ACUs requiring more I/O points can be equipped with additional expansion modules, while those with fewer I/O points can operate with just the CPU. This approach ensures a flexible, stable, and reliable solution.

 Designed to industrial-grade standards, PHLEEN F7-200 SMART with its outstanding interference resistance and -20°C to 60°C, can maintain long-term stable operation even under the demanding conditions of high temperatures, humidity, and complex, ever-changing tunnel environments.

System Functions and On-Site Display

1.Tunnel Fan Ventilation Control

Weight measurement modules integrated into an automated batching and filling line

The platform continuously monitors air quality and environmental indicators in each section (e.g., TF-01 to TF-08) of both the left and right tunnel tubes, collecting data on fan operation, malfunctions, and manual/automatic mode status. Based on monitored values such as carbon dioxide (CO₂), PM2.5, and visibility within the tunnel, it automatically adjusts fan speed and controls start/stop operations; it also receives fire alarm signals to trigger emergency smoke exhaust protocols.

2. Lane Indicator Control

 Through the lane indicator group control interface (LS01–LS06), the system provides centralized and precise control over the traffic status of each lane in both the left and right tunnels, reports lane-signal status in real time, and supports traffic dispatch and accident-related lane closures.

3. Vehicle Detection Data and Lane Traffic Flow Monitoring

The system collects traffic flow at entry, intermediate, and exit points of both tubes. For example, the left tube recorded 1,273 vehicles at entry, while the right tube recorded 10,014 vehicles at exit. All traffic detection data is updated in real time, providing robust support for traffic dispatch and big data analysis.

4. Water Level Monitoring and Discharge System (Water Level and Pump Interlocking)

On the monitoring screens for the right and left sewage pump stations, the water levels in the tanks are displayed in real time (e.g., 1.60 meters on the right and 2.69 meters on the left).The system provides comprehensive monitoring of the operating modes (remote automatic/manual), three-phase voltages (Ua/Ub/Uc), and currents (Ia/Ib/Ic) of Pumps 1–3, ensuring reliable flood prevention and drainage operations and drainage operations even under extreme weather conditions.

Why Choose Us?

High reliability, withstands harsh environments: Designed to industrial-grade standards with strong interference resistance. three-proof protection ensures long-term, trouble-free operation in complex tunnel environments.

 Modular and Flexible Configuration: PHLEEN’s extensive selection of CPUs and module combinations (SR60/DR32/DE16/QR08) allows for flexible configuration of monitoring points to suit tunnels of various sizes, thereby reducing overall costs.   

Extensive Communication Capabilities: Built-in Ethernet supports up to 32 Ethernet connections; features 3 built-in RS485 interfaces that enable automatic Modbus polling, ensuring simple programming and stable communication. It seamlessly integrates with various instruments, variable frequency drives, host computers, and fire alarm systems; supports expansion with up to 16 I/O modules, providing abundant I/O resources;

Proven Tunnel Control Logic: With a wealth of successful ACU implementation cases in highway tunnels, the system features mature interlocking logic for ventilation and lane lighting, helping projects significantly shorten the commissioning cycle.

Conclusion

The ventilation, lane guidance, and flood prevention and drainage systems in the Coastal Tunnel put PHLEEN’s PLC to the test, requiring millisecond-level data acquisition of multidimensional field data (wind speed, CO₂ concentration, vehicle traffic flow, and reservoir water levels), as well as precise coordinated control of fans, lane indicators, and drainage pumps.

 For scenarios such as highway tunnel electromechanical systems, underground utility tunnels, and traffic pump stations—where data points are dispersed and multi-device coordination is required—the PHLEEN Automation offers a cost-effective, stable, and reliable control solution.